Abstract
Partial discharge (PD) is measured simultaneously using free-space radiometric (FSR) and a galvanic contact measurement technique based on the IEC 60270 standard. The PD source is an emulator of the floating-electrode type. The radiated signal is captured using a biconical antenna. A method of estimating absolute partial discharge (PD) activity level from a radiometric measurement by relating effective radiated power to PD intensity using a PD calibration device is presented.