Jaber, Adel, Lazaridis, Pavlos, Saeed, Bahghtar, Zhang, Yong, Khan, Umar, Upton, David, Mohamad, Hamd, Mather, Peter, Atkinson, Robert, Judd, Martin, Vieira, Maria Fatima Queiroz and Glover, Ian (2017) Assessment of Effective Radiated Power of the Partial Discharge Emulator Source. In: Wireless and Satellite Systems. Lecture Notes of the Institute for Computer Sciences, Social Informatics and Telecommunications Engineering, 186 (186). Springer, Cham, pp. 108-115. ISBN 978-3-319-53850-1
Abstract

Two effective partial discharge (PD) measurement techniques are used; a galvanic contact measurement technique similar to the IEC 60270 standard measurement and free-space radiometric (FSR) measurement. Several types of PD sources are specially constructed: two internal PD emulators and an emulator of the floating-electrode type. An AC power supply is applied to the PD source and the radiated signal is captured using a wideband biconical antenna. The calibration of PD sources is demonstrated. Effective radiated power (ERP) of the PD sources using a PD calibration device is determined.